Acoustic canopied generator with a 1103A-33G engine and Stamford S1L2-J1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.

Prime / PRP · running power30.3 kVA24.2 kW
Standby / ESP · backup power32.9 kVA26.3 kW

Choose by operating duty. Prime is for variable-load operation; standby is for emergency backup. If you need 30 kVA prime, check that the prime rating meets your requirement. Understand the ratings.

Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.

Price and lead time confirmed with your quotation.

Reference build

Technical specification.

PPG modelPPG30PS
Engine brand / modelPerkins 1103A-33G
AlternatorStamford S1L2-J1
Frequency50 Hz
Reference voltage400 V
Reference phase3 phase
Exact prime rating30.3 kVA / 24.2 kW
Exact standby rating32.9 kVA / 26.3 kW
AspirationNaturally Aspirated
GovernorMechanical
No. of Cylinders3
Cylinder ArrangementIn Line
Displacement3.3L
Cooling TypeLiquid Cooled
Coolant Capacity11.8L
Oil Capacity8.3L
TypeBrushless
Poles4
AVR ModelAS540
Voltage Regulation1%
Insulation ClassH
ExcitationSelf Excited

Voltage-specific ratings

Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.

VoltageESP kVAESP kWPRP kVAPRP kW
200 V32.9 kVA26.3 kW30.3 kVA24.2 kW
208 V33 kVA26.4 kW30.3 kVA24.2 kW
230 V32.9 kVA26.3 kW30.3 kVA24.2 kW
240 V33 kVA26.4 kW30.3 kVA24.2 kW
400 V32.9 kVA26.3 kW30.3 kVA24.2 kW
415 V33 kVA26.4 kW30.3 kVA24.2 kW
Choose the details

Configuration options.

These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.

EngineAlternatorPhaseVoltagePrime / PRPStandby / ESP
1103A-33GStamford S1L2-J13400 V30.3 kVA32.9 kVA
1103A-33GKWise C184G283400 V30 kVA32.9 kVA
1103A-33GLeroy Somer TAL042C3400 V30.3 kVA33.1 kVA
1103A-33GStamford S1L2-Y11230 V28.5 kVA31.2 kVA
1103A-33GLeroy Somer TAL042H1230 V27.7 kVA29.9 kVA

Installation & enclosure

Dimensions (L × W × H)2240 × 1038 × 1378 mm
Reference weight1126.5 kg
Reference fuel tank80 litres
Configuration marketUK/EU
Manufacturer noise reference at 7 m76 dB(A)

Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.

Fuel consumption

50% Load4.07 litres/hour
75% Load5.59 litres/hour
100% Load7.33 litres/hour
110% Load8.01 litres/hour

Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.