550 kVA class
Cummins generator
KTA19G4

PPG-branded enclosure reference; final appearance follows the confirmed build specification.
Designed and manufacturedAcoustic canopied generator with a KTA19G4 engine and Leroy Somer TAL0473C reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG550CS |
|---|---|
| Engine brand / model | Cummins KTA19G4 |
| Alternator | Leroy Somer TAL0473C |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 500 kVA / 400 kW |
| Exact standby rating | 550 kVA / 440 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 18.9L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 93L |
| Oil Capacity | 50L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | R150 |
| Voltage Regulation | 1.0% Regulation% |
| Insulation Class | H |
| Excitation | Brushless |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 400 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| KTA19G4 | Leroy Somer TAL0473C | 3 | 400 V | 500 kVA | 550 kVA |
| Dimensions (L × W × H) | 4908 × 2164 × 2658 mm |
|---|---|
| Reference weight | 6078.5 kg |
| Reference fuel tank | 1120 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 57 litres/hour |
|---|---|
| 75% Load | 82 litres/hour |
| 100% Load | 107 litres/hour |
| 110% Load | 121 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
KTA19G4
QSX15G8
QSX15G8
Tell us your load, site and application. We’ll help you choose the right configuration.