580 kVA class
Cummins generator
QSZ13G10
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedAcoustic canopied generator with a QSZ13G10 engine and Stamford S5L1D-D41 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG580CS |
|---|---|
| Engine brand / model | Cummins QSZ13G10 |
| Alternator | Stamford S5L1D-D41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 529 kVA / 423 kW |
| Exact standby rating | 581 kVA / 465 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 18.9L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 77.1L |
| Oil Capacity | 78L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1.0% Regulation% |
| Insulation Class | H |
| Excitation | Brushless |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
| 400 V | 581 kVA | 465 kW | 529 kVA | 423 kW |
| 415 V | 550 kVA | 440 kW | 500 kVA | 400 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| QSZ13G10 | Stamford S5L1D-D41 | 3 | 400 V | 529 kVA | 581 kVA |
| Dimensions, weight and fuel tank | Confirmed with quotation and build drawing |
|---|
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 54 litres/hour |
|---|---|
| 75% Load | 80 litres/hour |
| 100% Load | 107 litres/hour |
| 110% Load | 118 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
QSZ13G10
KTA19G4
KTA19G4