1,100 kVA class
Perkins generator
4008TAG2A
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedOpen set generator with a 4008TAG2A engine and Stamford S6L1D-E41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG1100P |
|---|---|
| Engine brand / model | Perkins 4008TAG2A |
| Alternator | Stamford S6L1D-E41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 1024 kVA / 819 kW |
| Exact standby rating | 1123 kVA / 898 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 8 |
| Cylinder Arrangement | In Line |
| Displacement | 30.561L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 149L |
| Oil Capacity | 153L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | MX321 |
| Voltage Regulation | 0.5% |
| Insulation Class | H |
| Excitation | PMG |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 380 V | 1100 kVA | 880 kW | 1000 kVA | 800 kW |
| 400 V | 1123 kVA | 898 kW | 1024 kVA | 819 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 4008TAG2A | Stamford S6L1D-E41 | 3 | 400 V | 1024 kVA | 1123 kVA |
| 4008TAG2A | Leroy Somer TAL049E | 3 | 400 V | 1000 kVA | 1100 kVA |
| Dimensions (L × W × H) | 4650 × 2046 × 2484 mm |
|---|---|
| Reference weight | 7428.9 kg |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 111 litres/hour |
|---|---|
| 75% Load | 162 litres/hour |
| 100% Load | 215 litres/hour |
| 110% Load | 240 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
4008TAG2A
4008TAG2A
4008TAG2A
Tell us your load, site and application. We’ll help you choose the right configuration.