1,150 kVA class
Perkins generator
4008TAG2A
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedAcoustic canopied generator with a 4008TAG2A engine and Mecc Alte ECO43 1M4 A reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG1150PS |
|---|---|
| Engine brand / model | Perkins 4008TAG2A |
| Alternator | Mecc Alte ECO43 1M4 A |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 1025 kVA / 820 kW |
| Exact standby rating | 1125 kVA / 900 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 8 |
| Cylinder Arrangement | In Line |
| Displacement | 30.561L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 149L |
| Oil Capacity | 153L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | DER-1/A |
| Voltage Regulation | 0.5% |
| Insulation Class | H |
| Excitation | Auxiliary Wound |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 400 V | 1125 kVA | 900 kW | 1025 kVA | 820 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| 4008TAG2A | Mecc Alte ECO43 1M4 A | 3 | 400 V | 1025 kVA | 1125 kVA |
| Dimensions, weight and fuel tank | Confirmed with quotation and build drawing |
|---|
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 111 litres/hour |
|---|---|
| 75% Load | 162 litres/hour |
| 100% Load | 215 litres/hour |
| 110% Load | 240 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
4008TAG2A
4008TAG2A
4008TAG2A
Tell us your load, site and application. We’ll help you choose the right configuration.