220 kVA class
Cummins generator
QSB7G5

Representative generator image; final appearance follows the confirmed build specification.
Designed and manufacturedAcoustic canopied generator with a QSB7G5 engine and Stamford UCI274H1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG220CS |
|---|---|
| Engine brand / model | Cummins QSB7G5 |
| Alternator | Stamford UCI274H1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 200 kVA / 160 kW |
| Exact standby rating | 220 kVA / 176 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 6.69L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 16.8L |
| Oil Capacity | 18.9L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 200 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 208 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 220 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 230 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 240 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 380 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 400 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
| 415 V | 220 kVA | 176 kW | 200 kVA | 160 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| QSB7G5 | Stamford UCI274H1 | 3 | 400 V | 200 kVA | 220 kVA |
| QSB7G5 | Leroy Somer TAL044M | 3 | 400 V | 200 kVA | 220 kVA |
| Dimensions (L × W × H) | 3958 × 1504 × 2384 mm |
|---|---|
| Reference weight | 2569.99 kg |
| Reference fuel tank | 500 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 26 litres/hour |
|---|---|
| 75% Load | 36 litres/hour |
| 100% Load | 45 litres/hour |
| 110% Load | 51 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.