280 kVA class
Cummins generator
QSL9G3

Representative generator image; final appearance follows the confirmed build specification.
Designed and manufacturedAcoustic canopied generator with a QSL9G3 engine and Stamford UCDI274K1 reference alternator. Acoustic canopy and sound requirements to be confirmed for your application.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG280CS |
|---|---|
| Engine brand / model | Cummins QSL9G3 |
| Alternator | Stamford UCDI274K1 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 250 kVA / 200 kW |
| Exact standby rating | 275 kVA / 220 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 8.8L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 36L |
| Oil Capacity | 34L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 275 kVA | 220 kW | 248 kVA | 198 kW |
| 200 V | 275 kVA | 220 kW | 250 kVA | 200 kW |
| 208 V | 275 kVA | 220 kW | 250 kVA | 200 kW |
| 220 V | 275 kVA | 220 kW | 249 kVA | 199 kW |
| 230 V | 275 kVA | 220 kW | 250 kVA | 200 kW |
| 240 V | 275 kVA | 220 kW | 250 kVA | 200 kW |
| 380 V | 275 kVA | 220 kW | 249 kVA | 199 kW |
| 400 V | 275 kVA | 220 kW | 250 kVA | 200 kW |
| 415 V | 275 kVA | 220 kW | 250 kVA | 200 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| QSL9G3 | Stamford UCDI274K1 | 3 | 400 V | 250 kVA | 275 kVA |
| Dimensions (L × W × H) | 3958 × 1504 × 2384 mm |
|---|---|
| Reference weight | 2924.7 kg |
| Reference fuel tank | 500 litres |
| Configuration market | UK/EU |
| Manufacturer noise reference at 7 m | 76 dB(A) |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 31 litres/hour |
|---|---|
| 75% Load | 46 litres/hour |
| 100% Load | 56 litres/hour |
| 110% Load | 62 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
QSL9G3
QSB7G5
QSL9G5
Tell us your load, site and application. We’ll help you choose the right configuration.