340 kVA class
Perkins generator
2206A-E13TAG2
Compare UK-built 310 kVA diesel generators and nearby outputs. View open and canopied models, exact prime and standby ratings, and datasheets. Get a quote.
A rounded PPG model class is not a guaranteed duty rating. The tables below identify the actual documented output for each reference configuration.
2206A-E13TAG2
2206A-E13TAG2
1506A-E88TAG4
1506A-E88TAG4
DC09072A-02-12
DC09072A-02-12
1506A-E88TAG5
1506A-E88TAG5
DC09072A-02-13
DC09072A-02-13
DC09320A-02-63
DC09320A-02-63
1506A-E88TAG5
1506A-E88TAG5
6M16G350/5
6M16G350/5
For larger commercial sites and industrial equipment, assess the largest load step, motor starting, nonlinear loads and the operating duty. The steady-state kVA total alone does not settle the generator size.
At a power factor of 0.8, 310 kVA corresponds to 248 kW mathematically. That conversion is not a substitute for the manufacturer’s duty rating or a starting-load assessment.
Discuss your load scheduleThe model class alone does not establish continuous capability. Check prime and standby ratings and the manufacturer’s load-profile conditions. Confirm the intended run hours and average load when requesting a quotation.
Compare the canopied entries above, then confirm enclosure dimensions, sound requirements and final duty rating with PPG.
The comparison above includes Baudouin, Perkins, Scania. Some are close alternatives rather than an exact match; use the electrical rating table to compare them.
| Model | Engine brand | Format | Prime | Standby | Voltage |
|---|---|---|---|---|---|
| PPG340PS | Perkins | Acoustic canopied | 310 kVA | 340 kVA | 400 V |
| PPG340P | Perkins | Open set | 310 kVA | 340 kVA | 400 V |
| PPG310PS | Perkins | Acoustic canopied | 283 kVA | 308 kVA | 400 V |
| PPG310P | Perkins | Open set | 283 kVA | 308 kVA | 400 V |
| PPG310SS | Scania | Acoustic canopied | 281 kVA | 308 kVA | 400 V |
| PPG310S | Scania | Open set | 281 kVA | 308 kVA | 400 V |
| PPG350PS | Perkins | Acoustic canopied | 316 kVA | 347 kVA | 400 V |
| PPG350P | Perkins | Open set | 316 kVA | 347 kVA | 400 V |
| PPG330SS | Scania | Acoustic canopied | 303 kVA | 332 kVA | 400 V |
| PPG330S | Scania | Open set | 303 kVA | 332 kVA | 400 V |
| PPG300SS | Scania | Acoustic canopied | 301 kVA | Confirm on enquiry | 400 V |
| PPG300S | Scania | Open set | 301 kVA | Confirm on enquiry | 400 V |
| PPG330PS | Perkins | Acoustic canopied | 300 kVA | 330 kVA | 400 V |
| PPG330P | Perkins | Open set | 300 kVA | 330 kVA | 400 V |
| PPG360BS | Baudouin | Acoustic canopied | 321 kVA | 352 kVA | 400 V |
| PPG360B | Baudouin | Open set | 321 kVA | 352 kVA | 400 V |
Tell us your load, site and application. We’ll help you choose the right configuration.