340 kVA class
Cummins generator
QSL9G5
A model-specific render and installation drawing will be supplied with the quotation.
Designed and manufacturedOpen set generator with a QSL9G5 engine and Stamford S4L1D-D41 reference alternator. Open sets require a suitable installation with ventilation, exhaust and weather protection.
Exact ratings above: 400 V, 3-phase, 50 Hz reference configuration. The model number is a rounded class.
Price and lead time confirmed with your quotation.
| PPG model | PPG340C |
|---|---|
| Engine brand / model | Cummins QSL9G5 |
| Alternator | Stamford S4L1D-D41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 298 kVA / 238 kW |
| Exact standby rating | 340 kVA / 272 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 8.8L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 36L |
| Oil Capacity | 34L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 330 kVA | 264 kW | 299 kVA | 239 kW |
| 200 V | 340 kVA | 272 kW | 298 kVA | 238 kW |
| 208 V | 340 kVA | 272 kW | 299 kVA | 239 kW |
| 220 V | 320 kVA | 256 kW | 290 kVA | 232 kW |
| 220 V | 330 kVA | 264 kW | 297 kVA | 238 kW |
| 230 V | 340 kVA | 272 kW | 298 kVA | 238 kW |
| 240 V | 340 kVA | 272 kW | 299 kVA | 239 kW |
| 254 V | 320 kVA | 256 kW | 290 kVA | 232 kW |
| 380 V | 330 kVA | 264 kW | 297 kVA | 238 kW |
| 400 V | 340 kVA | 272 kW | 298 kVA | 238 kW |
| 415 V | 340 kVA | 272 kW | 299 kVA | 239 kW |
| 440 V | 320 kVA | 256 kW | 290 kVA | 232 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| QSL9G5 | Stamford S4L1D-D41 | 3 | 400 V | 298 kVA | 340 kVA |
| Reference weight | 2244.7 kg |
|---|---|
| Reference fuel tank | 730 litres |
| Configuration market | Export |
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 31 litres/hour |
|---|---|
| 75% Load | 46 litres/hour |
| 100% Load | 63 litres/hour |
| 110% Load | 75 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.
QSL9G5
QSL9G3
QSL9G3
Tell us your load, site and application. We’ll help you choose the right configuration.