| PPG model | PPG410C |
|---|---|
| Engine brand / model | Cummins QSZ13G6 |
| Alternator | Stamford S4L1D-E41 |
| Frequency | 50 Hz |
| Reference voltage | 400 V |
| Reference phase | 3 phase |
| Exact prime rating | 360 kVA / 288 kW |
| Exact standby rating | 407 kVA / 326 kW |
| Aspiration | Turbocharged |
|---|---|
| Governor | Electronic |
| No. of Cylinders | 6 |
| Cylinder Arrangement | In Line |
| Displacement | 13L |
| Cooling Type | Liquid Cooled |
| Coolant Capacity | 72.5L |
| Oil Capacity | 78L |
| Type | Brushless |
| Poles | 4 |
| AVR Model | AS440 |
| Voltage Regulation | 1% |
| Insulation Class | H |
| Excitation | Self Excited |
Ratings for the reference engine and alternator configuration. Confirm the required connection and voltage with your quotation.
| Voltage | ESP kVA | ESP kW | PRP kVA | PRP kW |
|---|---|---|---|---|
| 190 V | 380 kVA | 304 kW | 350 kVA | 280 kW |
| 200 V | 407 kVA | 326 kW | 360 kVA | 288 kW |
| 208 V | 400 kVA | 320 kW | 360 kVA | 288 kW |
| 220 V | 380 kVA | 304 kW | 350 kVA | 280 kW |
| 220 V | 380 kVA | 304 kW | 350 kVA | 280 kW |
| 230 V | 407 kVA | 326 kW | 360 kVA | 288 kW |
| 240 V | 400 kVA | 320 kW | 360 kVA | 288 kW |
| 254 V | 380 kVA | 304 kW | 350 kVA | 280 kW |
| 380 V | 380 kVA | 304 kW | 350 kVA | 280 kW |
| 400 V | 407 kVA | 326 kW | 360 kVA | 288 kW |
| 415 V | 400 kVA | 320 kW | 360 kVA | 288 kW |
| 440 V | 380 kVA | 304 kW | 350 kVA | 280 kW |
These documented electrical combinations sit within this rounded model family. Final enclosure and component selection are agreed with your quotation.
| Engine | Alternator | Phase | Voltage | Prime / PRP | Standby / ESP |
|---|---|---|---|---|---|
| QSZ13G6 | Stamford S4L1D-E41 | 3 | 400 V | 360 kVA | 407 kVA |
| Dimensions, weight and fuel tank | Confirmed with quotation and build drawing |
|---|
Dimensions and weight relate to the stated reference build, not every option. Acoustic figures, where listed, are manufacturer references at 75% rated kW using distance corrections. Confirm the project noise requirement and final drawing before installation.
| 50% Load | 48 litres/hour |
|---|---|
| 75% Load | 65 litres/hour |
| 100% Load | 82 litres/hour |
| 110% Load | 91 litres/hour |
Manufacturer reference consumption. Actual fuel use depends on load, operating conditions and the final specification.